Ring network cabinet

+
  • QGG固体绝缘环网柜-白色面板.jpg
  • SF6充气柜-白色面板.jpg
  • 环保气体柜-白色面板.jpg

Ring network cabinet


Key words:

Classification:

Product Center

Other products

Product accessories:

  • Description
  • Product Parameters
    • Commodity name: Ring network cabinet
    • Commodity ID: QEFG QLG QGG

    The ring network refers to a ring-shaped distribution network, where the power supply trunk forms a closed loop, supplying power to this ring trunk, which then distributes power outward through high-voltage switches. The advantage of this is that each distribution branch can draw power from both its left and right trunk lines. When the left trunk line fails, it continues to receive power from the right trunk line, and when the right trunk line fails, it continues to receive power from the left trunk line. Thus, although the total power supply is single-route, each distribution branch benefits from a dual-route power supply, thereby improving the reliability of power supply. The relationship between the high-voltage ring network cabinet and the box transformer is that the box transformer can be one of the terminals of the high-voltage ring network cabinet. The high-voltage ring network cabinet integrates several incoming lines into a ring network, achieving dual or multiple incoming lines. The ring network cabinets independently developed and produced by Qingchang Electric Power are divided into three types based on insulation methods:

    • Environmentally friendly gas-insulated ring network cabinet
    • SF6 gas-insulated ring network cabinet
    • Solid insulated ring network cabinet

    Depending on the different insulation methods, various models of ring network cabinets have different advantages. Users can choose products based on environmental conditions and project requirements.

     

  • QEFG Environmental Protection Gas Insulated Ring Network Cabinet Rated Parameters

    Conventional

    Unit

    Parameter

    Rated Voltage

    kV

    12

    Rated Frequency

    Hz

    50

    Power Frequency Withstand Voltage

    V/min

    42/28

    Lightning Impulse Voltage

    kV

    75/85

    Arc Duration

    s

    1

    Primary Component Protection Level (excluding metering cabinet)

    IP67

    Cabinet Protection Level

    IP4X

    Isolation Chamber Protection Level

    IP2X

    Operating Power Supply Voltage

    V

    DC: 24 48 110 220

    AC: 110 220

     

     

    QLG SF6 Gas Insulated Ring Network Cabinet Rated Parameters

    Serial Number

    Project

    Unit

    Parameter

    1

    Rated Voltage

    kV

    12

    24

    2

    Rated Current

    A

    630/1250

     630/1250

    3

    Rated Frequency

    Hz

    50

    50

    4

    1min WorkFrequencyWithstand Voltage

    Phase-to-Phase and Ground

    kV

    42

    65

    Isolation Break

    kV

    48

    79

    5

    Lightning Impulse Withstand Voltage

    Phase-to-Phase and Ground

    kV

    75

    125

    Break

    kV

    85

    145

    6

    Rated SF6 Gas Pressure

    (Gauge Pressure at 20℃)

    MPa

    0.04

    0.04

    7

    SF6 YearLeakage Rate

    %

    ≤0.05

    8

    Protection Level

    SF6 GasBox

    IP67

    Cabinet Body

    IP4X

     

    QGG Solid Insulated Ring Network Cabinet

    Project

    Unit

    Parameter

    Rated Voltage

    V

    12

    Rated Frequency

    Hz

    50

    Rated Current

    A

    630 (1250)

    Rated Short-Time Withstand Current

    kA/s

    20/4 (25/4)

    Rated Peak Withstand Current

    kA

    50(63)

    Power Frequency Withstand Voltage

    kV/min

    42/48

    Lightning Impulse Voltage

    kV

    75/85

    Arc Duration

    s

    >=0.5

    Primary Component Protection Level (excluding metering cabinet)

     

    IP67

    Operating Power Supply Voltage

    V

    DC: 24 48 110 220

    AC: 110 220

    Unit Cabinet Reference Size (W×D×H)

    mm

    II BType  440×960×1500

    III AType  415×945×1600

    IV AType  400×850×1520