FLW pole-mounted SF6 load switch

+
  • sf6 fuhekaiguan.jpg

FLW pole-mounted SF6 load switch


FLW series outdoor communication high-voltage SF6 load switches are suitable for outdoor three-phase AC distribution systems with a rated voltage of 12kV and a rated frequency of 50Hz, used for switching load current and closing overload current. This product uses SF6 gas as the arc extinguishing medium, which has excellent arc extinguishing performance; the structure of the load switch is a three-phase common box type, with three-phase linkage operation, which can be operated manually on-site or remotely from the central control room; this product is suitable for substations, industrial and mining enterprises, as well as urban and rural network automation distribution networks and places with frequent operations.

Key words:

Classification:

Product Center

Medium Voltage Column Switch Series

Load switch on the column

Product accessories:

  • Description
  • Product Parameters
    • Commodity name: FLW pole-mounted SF6 load switch
    • Commodity ID: FLW-QT1-12/630

    FLW series outdoor communication high-voltage SF6 load switches are suitable for outdoor three-phase AC distribution systems with a rated voltage of 12kV and a rated frequency of 50Hz, used for switching load current and closing overload current. This product uses SF6 gas as the arc extinguishing medium, which has excellent arc extinguishing performance; the structure of the load switch is a three-phase common box type, with three-phase linkage operation, which can be operated manually on-site or remotely from the central control room; this product is suitable for substations, industrial and mining enterprises, as well as urban and rural network automation distribution networks and places with frequent operations.

    FLW series outdoor communication high-voltage SF6 pole-mounted load switch is suitable for outdoor three-phase AC distribution systems with a rated voltage of 12kV and a rated frequency of 50Hz, used for switching load current and closing overload current. This product uses SF6 gas as the arc extinguishing medium, which has excellent arc extinguishing performance; the structure of the load switch is a three-phase common box type, with three-phase linkage operation, which can be operated manually on-site or remotely from the central control room; its shell is made of cold-rolled steel plate, which can withstand gas pressure and is suitable for use in various climatic conditions, with simple pole-mounted installation, convenient and quick layout, reducing construction costs; this product is suitable for substations, industrial and mining enterprises, as well as urban and rural network automation distribution networks and places with frequent operations.

  • Technical Parameters:

    • Arc extinguishing method/insulating medium: SF6
    • Rated voltage: 12kV
    • Rated current: 630A
    • Rated cable charging breaking current: 25A
    • Rated short-circuit breaking current: 20A
    • Temperature rise test current: 1.1lr
    • Rated power frequency 1min withstand voltage     relative to ground/phase to phase  42kV
    •                                           breakdown voltage 48kV
    • Rated lightning impulse withstand voltage (1.2/50ms) peak     relative to ground/phase to phase  75kV
    •                                                                  breakdown voltage 85kV
    • Rated short-time withstand current and duration: 20/4 kA/s
    • Rated peak withstand current: 50kV
    • Rated short-circuit breaking current: 20kV
    • Rated short-circuit closing current: 50kV
    • Switch shell protection level: not less than IP67